Test & Measurements

Print

 

  • MULTIFUNCTON INSTALLATION TESTER ( Kyoritsu )

    Product code:

    KEW6516

    Description:
    Insulation resistance SPD(Varistor)
    • Test voltage:100V 250V 500V 1000V Max.1000V
    • Measuring ranges: 2.000/20.00/200.0M/1000M/2000M (Auto-ranging)
    • Accuracy: ±2%rdg±6dgt...±5%rdg±6dg
    • Rated current: 1.0-1.2mA
    • Short circuit current: 1.5mA max
    Loop impedance
    • Function: LOOP ATT LOOP HIGH
    L-PE/L-N(3wire) L-PE(2wire) L-PE(0.01Res) L-PE(0.001Res) L-N/L-L
    • Rated voltage 100-260V(50/60Hz),48-260V(50/60Hz),100-260V(50/60Hz),48-500V(50/60Hz)
    • Impedance range: 2.000/20.00/200.0/2000(Auto-ranging)
    • Accuracy:±3%rdg±6dgt
    • Nominal test current at 0 external loop: L-N:6A/60ms; N-PE:10mA; L-PE:15mA 20:6A/20ms; 200:0.5A/20ms; 2000:15mA/500ms; 25A/20ms 6A/20ms
    PSC/PFC
    • Range 2000A/20kA(L-N(PSC)/L-PE(PFC)),2000A/20kA(PFC,PSC),2000A/50kA(PFC)
    • Accuracy:PSC/PFC accuracy is derived from measured loop impedance specification and measured voltage specification
    RCD
    • Rated voltage 100-260V(50/60Hz)
    • Function: x1/2, x1,x5,Ramp,Auto,Uc; 6/10/30/100/300/500/1000mA/variable
    • RCD type:AC(G/S) A(G/S) F(G/S) B(G/S)
    • Trip current setting: x1/2,x1,Uc 10/30/100/300/500/1000mA(G),
    • Ramp: 10/30/100/300/500mA 10/30/100/300/500mA 10/30/100/300/500mA 10/30/100/300mA
    • Accuracy Trip current: -8% - -2% ; -10% - 0%; 0% - +10% ; Ramp -4% - +4%, -10% - +10%
    • Trip time: x1/2 2000ms(G/S):±1%rdg±2ms ; x1 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms; x5 410ms(G/S):±1%rdg±2ms
    Continuity
    • Range: 20.00/200.0/2000 (Auto-ranging);
    • Open circuit voltage: (DC) 7-14V ;
    • Measuring current: 200mA >200mA or more(2 or less); 15mA 15mA±3mA(short-circuit)
    • Accuracy: ±2%rdg±8dgt
    Volts
    • Range 300.0/600V(Auto-ranging);
    • Measuring ranges: Volts 2-600V (Accuracy: ±2%rdg±4dgt)
    • Frequency 45-65Hz ( accuracy: ±0.5%rdg±2dgt )
    Phase Rotation,
    • Rated voltage: 48-600V(50/60Hz);
    • Remarks Remarks Correct phase sequence: are displayed "1.2.3" and mark Reversed phase sequence: are displayed "3.2.1" and mark
    Earth
    • Range: 20.00/200.0/2000(Auto-ranging)
    • Accuracy: ±2%rdg±0.08(20.00), ±2%rdg±3dgt(200.0/2000)
    General
    • Applicable Standards: IEC 61010-1 CAT Ⅳ 300V,CAT Ⅲ 600V Pollution degree 2, IEC 61010-2-034, IEC 61557-1,2,3,4,5,6,7,10, IEC 60529(IP40), IEC 61326(EMC)
    • Communication Interface: USB
    • Power source: LR6(AA)(1.5V) × 8
    • Dimensions: 136(L) × 235(W) × 114(D)mm
    • Weight: 1300g
    • Included Accessories: Main test lead*², 7281(Test leads with remote control switch), 7246(Distribution board test lead), 7228A(Earth resistance test leads), 8041(Auxiliary earth spikes[2 spikes/1 set])
    9084(Soft case), 9142(Carrying case), 9151(Shoulder strap), 9199(Shoulder pad), LR6(AA) × 8, Instruction manual, 8212-USB(USB adaptor with "KEW Report(Software)")*³,
    Calibration certificate
    • Datasheet: KEW6516

    Yes

    Price (VAT included):

    1251.16 €